Special Venting Notes:
DVP20CCNAT - can be terminated horizontally with kit DVK45NAT
maximum 18".
DVP20CCLP - can be terminated horizontally with kit DVK45LP
maximum 18".
DVP20CC(LP,NAT) - can use a 14" short snorkel or 36" tall snorkel.
DVP30CC (NATURAL) - Can be vented horizontally straight
out the back of stove if a minimum 14" snorkel is used. Or,
if venting horizontally, a 12" vertical vent is required off the
back of the stove before turning with an elbow horizontally
out the wall. See page 12.
DVP30CC (PROPANE) - Can be vented horizontally straight
out the back of the stove if a 36" snorkel is used. Or, if
venting horizontally, a 24" vertical vent is required off the
back of the stove before turning with an elbow horizontally
out the wall. See page 12.
Total vertical run MUST BE completed before starting horizontal
run. Horizontal chimney run must slope upward (away from
stove) 1/4" per foot and vent termination must be level.
Sidewall Venting
The maximum vertical and horizontal distances are 25 feet and 12
feet, respectively. Vertical dimensions are based on top of stove to
centerline of pipe. Horizontal dimensions are based on centerline
of pipe to termination.
Under no circumstances should combustible materials (including
siding) be closer than 3" from the top of the 6 5/8" pipe or closer
than 1" on the sides and bottom.
Cutting the Hole
After the appliance has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This
hole needs to be 10" high x 9" wide for 4 x 6 pipe and 12-1/2 high
x 10-1/2 wide for 5 x 8 pipe with its center line determined by the
amount of vertical arise and horizontal run of the termination. When
locating the hole it must be noted that the bottom of the cap must
be 12" above the ground level, and top of the cap must be no less
than 18" below a combustible projection, and no closer than 9" to
any wall running parallel to vent termination.
42603-4-0421

VENTING STOVE

CAUTION
VENT CAP
CHAPEAU D'ÉVACUATION
CHAPEAU D'ÉVACUATION
9' (222MM TO SIDE WALL
229 mm (9 po) VERS MUR LATÉRAL
229 mm (9 po) VERS MUR LATÉRAL
Figure 6
Co-Linear to Co-Axial Connection
A Co-Axial to Co-Linear appliance connector is approved for
installation in vertical venting applications. One can be purchased
through Empire Comfort Systems or Simpson Dealer (part number
46DVA-GCL).
VERTICAL
VENT KIT
(DVKI)
(DVKI)
INTAKE
PRISE D'AIR
EXHAUST
ÉVACUATION
STRAIGHT
COAXIAL DROIT
CO-AXIAL
(DETERMINE
LENGTH NEEDED
& PURCHASE
SEPARATELY)
VENT CAP
CHAPEAU D'ÉVACUATION
ROUND CO-LINEAR TO
RACCORD ROND
CO-AXIAL CONNECTOR
COLINÉAIRE-COAXIAL
CHIMNEY LINER
PRÊT-À-MONTER
DE TERMINAISON
TERMINATION KIT
DE CONDUIT
DE CHEMINÉE
FLEX PIPE
TUYAU FLEXIBLE
CO-AXIAL TO
CO-LINEAR
RACCORD
COAXIAL-COLINÉAIRE
CONNECTOR
(SD46DVA-GCL)
(SD46DVA-GCL)
45° ELBOW
COUDE DE 45°
(SD46DVA-E45B)
(SD46DVA-E45B)
Figure 7
Page 11