ALARM
A28 P.FAILURE 21
A29 P.TEST MODE
A30 P FAILURE 23
A31 DUBL UPS NR.
Possible Causes: 1) Change from settings menu
A39 PSP FAILURE
A40 CANT FIND PR
A41 P.BAL.FAILURE
A42 BATTERY TEST
A43 P.SYNC.FAIL
A44 BT.OPERATION
Possible Causes: 1) Central system is black-out
A45 MAINS OK
A46 BOOST CH.END
A47 CANNOT START
Status messages:
This message group simply shows the UPS STATUS at the upper line of LCD PANEL.
RECTIFIER START !
INVERTER START !
MAINT SWITCH ON !
MANUEL BYPASS !
STATUS ALARM !
STATUS NORMAL !
EMERGENCY STOP !
WAITING SYNC !
STATUS FAULT !
CLOSE BATT.CB !
STATUS WARNING !
RECTIFIER START :
At start up the UPS controller board check for input voltage, frequency, battery voltage for starting, if these
parameters normal UPS starts.
INVERTER START :
If the inverter stops controller board tries to start again, during inverter start this message appears on first line of
LCD PANEL.
MAINT SWITCH ON:
Maintenance bypass switch is connected from input to the output of UPS directly, controller stops inverter for
accidental short circuits between mains voltage and inverter output. If the user turn off maintenance switch
inverter starts again.
EMERGENCY STOP :
If an external EPO switch is installed to system (connected to interface board),to stop all UPS parts
(rectifier,static bypass,inverter,etc....) is possible. After pressing EPO switch all parts of the UPS stops,for
restart turn off S1 (inverter input) switch and turn on again.
Parallel controller board failure
Paralel controller is in test mode
Parallel controller board failure
Same UPS number is used in parallel system.
Power supply is not functioning possibly because either of a wrong phase
sequence or rectifier fault.
One of parallel modes is selected but there is no parallel control board on UPS
Change mode from settings menu
In parallel operation current sharing is not okay
Performing battery test
In parallel system SLAVE UPS is not synchronized to MASTER UPS
UPS is operating from batteries
2) Distribution problems upfront of the UPS
After mains failure, mains voltage restored again. This message appears on
screen for 15 seconds after mains restored.
Boost charge mode is finished, normal charge is valid.
Analog start system in UPS is failed.
:
UPS started the rectifier
:
UPS started the inverter
:
Maintenance bypass switch is on
:
Load is transferred to mains manually
:
Alarm status
:
UPS is operating
:
External emergency signal is detected.
:
Inverter started waiting for syncronization
:
Fault status
:
UPS is waiting for battery CB close
:
Warning message is valid on LCD panel