Advertisement

Quick Links

UNINTERRUPTIBLE POWER SUPPLIES
( 3 Phase Input & 1 Phase Output )
T-200 SERIES
T-206
T-207
T-210
USER MANUAL
6 kVA
7,5 kVA
10 kVA

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the T-200 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tescom T-200 Series

  • Page 1 T-200 SERIES UNINTERRUPTIBLE POWER SUPPLIES ( 3 Phase Input & 1 Phase Output ) T-206 6 kVA T-207 7,5 kVA T-210 10 kVA USER MANUAL...
  • Page 3: Table Of Contents

    CONTENTS SAFETY ................... 1 INTRODUCTION 2.1. System Description ........... 2 2.2. Technical Specifications ..........4 III. INSTALLATION 3.1. Unpacking ............... 6 3.2. Location Selection ............6 3.3. Cable Connections ............6 3.3. Start – up ................8 IV. OPERATION PROCEDURE 4.1.
  • Page 4: Safety

    T-200 Series UPS User Manual I. SAFETY This manual contains important instructions for T-200 series UPS that should be followed during installation and maintenance. IMPORTANT NOTICES 1. Read instructions carefully before operating the UPS 2. All warnings in the manual should be adhered to.
  • Page 5: Introduction

    When incoming power is interrupted, the UPS protects the computers instantaneously without any transfer time. The T-200 Series has high non-linear load capability (i.e. Crest Ratio 3:1) and this is suitable for powering special loads such as switching power supplies or highly capacitive inputs like computers.
  • Page 6 T-200 Series UPS User Manual The system's static transfer switch (STS) provides by-pass power as its standby source. During an overload condition, the S.T.S will switch the customer's load over to the bypass line with no interruption. The S.T.S will transfer back to the inverter automatically when the overload condition has been cleared. If the inverter fails internally, the unit switches to bypass within a few milliseconds.
  • Page 7: Technical Specifications

    T-200 Series UPS User Manual 2.2 Technical Specifications T-206 T-207 T-210 Power 6 kVA 7,5 kVA 10 kVA Power Factor Automatic Battery Test Alarm Relays RS 232 INPUT Input Voltage 380/400/415 AC 3Ph + N Input Voltage Tolerance + 15%, -15% 220/230/240 VAC ±10%...
  • Page 8 T-200 Series UPS User Manual DB9 Port PK1 On-Off Switch DB9 Port Battery Fuse AC Output Main Switch 6 - 7,5 - 10 kVA (Model-A) Rear view PK1 On-Off Switch AC Output Figure 2.2.1 Terminals 6 - 7,5 - 10 kVA Rear view...
  • Page 9: Installation

    T-200 Series UPS User Manual III. INSTALLATION 3.1 Unpacking The UPS is packed and enclosed in a structural cardboard carton to protect it from damage. 1. Inspect for damage that may have occurred during the shipment If any damage is noted, call the shipper immediately and retain the shipping carton and the UPS.
  • Page 10 T-200 Series UPS User Manual The safety earth cable must be connected to the earth bus bar and bonded to each cabinet in the system. All cabinets should be earthed in accordance with local regulations. The UPS itself has no effect on the earthing quality i.e. it doesn’t change the unwanted voltage difference between the earth and neutral lines.
  • Page 11: Start-Up

    T-200 Series UPS User Manual 3.4 Start-Up 1. Turn on the Main Switch and battery fuse to “1” position on the rear panel. (In this case, there is line voltage at the output and battery charger board is active) 2. Turn the On-Off Switch PK1 on the rear panel to "1" position. In a few seconds the cooling fan will start to operate, then the red LED "by-pass"...
  • Page 12: Operation Procedure

    T-200 Series UPS User Manual IV. OPERATING PROCEDURE 4.1 Turn On procedure 1. Turn on the Main Switch and battery fuse on the rear panel to "1" position. (There is line voltage at the output.) 2. Turn on the On-Off Switch PK1 on the rear panel to the "1" position. Turn on the power switches on your critical load after the "Inverter"...
  • Page 13: Push Buttons

    T-200 Series UPS User Manual 4.4.1 Push buttons 1- Sound on-off button : When you push this button it will disable the audible alarm on the UPS. If you want to enable the sound alarm again you have to push the DISPLAY SELECT button for 2 sec.
  • Page 14: Second M.l.(Alarms)Of The Lcd

    T-200 Series UPS User Manual 4.4.3 Second message line of the LCD VERSION XXXX Micro controller software version of the UPS. This message shown that there is a problem of the static bypass system, BYPASS FAILURE please call for service.
  • Page 15: Optional Equipment

    T-200 Series UPS User Manual V. OPTIONAL EQUIPMENT 5.1 Software Options The UPS can send digital data (optional) to the computer thought the RS232 port. No additional card is needed. It also has two alarm relays: Line failure and battery low.
  • Page 16: Snmp Module

    T-200 Series UPS User Manual 5.2 SNMP Module Using the SNMP module, your UPS is seen as a network device in your WAN or LAN applications, and with this way it can be monitored more than one UPS’s connected to your network through SNMPVIEW Software supplied with the module or it is possible to monitor the UPS through an Internet Browser.
  • Page 17: Remote Monitoring Panel

    T-200 Series UPS User Manual 5.4 Remote monitoring panel (RMP) You can see UPS status and parameters without using a computer up to 200 meters ( via RS485 interface). And you can connect more than one remote panel in cascade for monitoring your UPS system from several different locations at the same time.
  • Page 18 T-200 Series UPS User Manual...
  • Page 19 T-200 Series UPS User Manual ( T-MON ) COM1 Connection Diagram Of The RMP...
  • Page 20: Customer Service

    T-200 Series UPS User Manual VI. CUSTOMER SERVICE WARNING! There are no customer serviceable components inside. DO NOT open the cover or attempt to service the unit. High voltage may remain when the unit is shut down. Unauthorized service will void the warranty and could cause serious injury.
  • Page 21: Limited Warranty

    T-200 Series UPS User Manual VII. LIMITED WARRANTY The UPS is warranted against all defects in workmanship and materials under normal use for a period of one ( ) year from the date of shipment to the original user. The conditions of this warranty and the extent of responsibility of …………………………………………………………………………………………………………………………..
  • Page 22 AGKK3802 09/2013...