Flame detectors
Hide thumbs Also See for Rosemount 975:
Table of Contents

Advertisement

Reference Manual
00809-1500-4975
Status
F46
F47
F48
F51
F52
F53
F54
F55
F56
F57
F58
F59
F60
N0
N1
Rosemount 975
Description
4-20mA
output
IR signal Amp
1mA
stuck at one
failure
Failure SPI COM
1mA
with AFE
AFE stuck at 1
1mA
Sensor 4.5 noise 1mA
Sensor 5 noise
1mA
Sensor 4 noise
1mA
Sensor 4.4 noise 1mA
Sensor 4.5 and 5
1mA
short circuit
Sensor 4.5 and 4
1mA
short circuit
Sensor 4 and 5
1mA
short circuit
Sensor 4.4 and
1mA
4.55 short circuit
Sensor 4.4 and 4
1mA
short circuit
Sensor 4.5 and 5
1mA
short circuit
Normal
4mA
Constant
4mA
external BIT
Analog
Fault
LED
output
relay
indicator
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
0v
Open
4Hz
blinking
orange
2v
Close
1Hz
blinking
green
2v
Close
4Hz
blinking
orange
Reference data
June 2021
Test rate
Every BIT
Every 30msec
Every 30msec
Every 30msec
Every 30msec
Every 30msec
Every 30msec
Every BIT
Every BIT
Every BIT
Every BIT
Every BIT
Every BIT
Every 30msec
Every 30msec