Operation
June 2021
A. Detector configurable settings
B. BIT settings
C. Accessory relay options
D. Detection options
E. Lock option
F. 4-20 settings
G. Click to save any changes made, becomes clickable once any settings are changed
Note
Any unavailable options will be grayed out depending on specific detector model
connected.
3.9.1
Detector configurables
These detector parameters may be configured.
Sensitivity
Heater mode
Alarm delay
Heater power
22
Sets the detector's sensitivity (in meters). A higher number
indicates greater sensitivity. See relevant product manual for
more information.
Demister settings for clearing condensation from the lens.
Choose from On, Off, or Auto.
Default: Auto
The delay between detection of a signal and activation of the
alarm. Choose from 0, 3, 5, 10, 20, 30, or A (anti-flare).
Default: A
Choose from high or low power.
Default: High power