RAMPING

The ramping function automatically reduces
the main set point by the set amount every 24
hours.
The ramping setting is adjusted in 0.01 degree
decrements from a minimum setting of OFF, -
0.01°F (-0.01°C) to a maximum setting of -
0.99°F (-0.50°C)
The main set point must be greater than
the limit.
Adjusting ramping:
rotate the Selector dial to position (9),
rotate the Adjustor dial counterclockwise
to decrease the ramping rate, clockwise to
increase it.
The ramping setting is displayed on the ECS.
NOTE: When ramping is activated or enabled, the main
set point temperature cannot be manually adjusted.
Ramping automatically turns OFF when the minimum
temperature limit is reached!
Example: The main set point temperature is set to 70°F
and ramping is adjusted to -0.05°F. The following day the
main set point temperature drops to 69.95°F followed by
69.90°F on the next. Although the main set point real
value decreases, the display will be changed after 10
days. The main set point will then be 69.5°F.
www.monitrol.com