Condition
Generator Switch is
in the OFF Mode
System Ready for
Automatic Start
Generator Switch is
in the MANUAL Mode
Weekly Exerciser
is not Set (Note A)
Battery Voltage <12.2V
for > 1 minute
Battery Voltage <6V
For > 0.05 seconds
Unit Shutdown due
To Low Oil Pressure
Unit Shutdown due
To High Cooant Temp
Unit Shutdown due
To Engine Overspeed
Unit Failed to Start
During it's Crank Cycle
Utility Voltage is
< 60% of Nominal
Unit Shutdown due
To Low Coolant Level
Engine Speed Signal
Fault/RPM Signal Loss
Control Board is
In GTS Mode
5 sec ON, 1 sec OFF
@ = Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column
X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto)
Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set
4
General Information
R-panel Technical Manual
System
Low
Ready
Fuel
OFF
@
ON
@
OFF
@
X
@
X
@
OFF
@
OFF
@
OFF
@
OFF
@
OFF
@
Flashing
@
1 sec rate
OFF
@
OFF
@
Flashing
@
Low
Low
High
Bat
Oil
Temp
X
OFF
OFF
X
OFF
OFF
X
OFF
OFF
Flashing Flashing
Flashing
(---------------------------------------1 sec rate -------------------------------------)
ON
(Non-Latching)
ON
X
ON
X
ON
X
X
X
X
Flashing
X
X
Switch Position
Over
Over
Manual Auto Off
Speed
Crank
OFF
OFF
OFF
OFF
OFF
OFF
Flashing
Flashing
ON
ON
Flashing
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Need help?
Do you have a question about the R-200 and is the answer not in the manual?
Questions and answers