10A, 12VDC BATTERY CHARGER
Nominal Input AC Line Voltage ........................ 120Vac
Operating AC Line Voltage Range ......108Vac to 132Vac
Input AC Line Frequency .............................50 or 60Hz
AC Line Fuse ...................................... 5 Amp, 5x20mm,
Battery Fuse ..............................15 Amp, Littelfuse ATO
Nominal Charge Rate ..................................... 10 Amps
Equalize Voltage (typ) ....................................13.8 Volts
Float Voltage (typ) .........................................13.0 Volts
Current at Equalize to Float Transition (typ) .. 5 Amps
Battery Undervoltage Shutdown (typ) ...............11 Volts
LED Indicators
AC Line Voltage > 108Vac ...............Green LED ON
Battery Connected & Charging ........Yellow LED ON
the Green LED must be ON to obtain a valid
battery charging indication,
Yellow LED ON if charge current > approx 2
Amps)
Battery Current Drain (AC Power OFF) ....... 30mA (typ)
AC Line Connections ......................... via terminal block
Battery Connections .......................... via terminal block
Control Connections ......................AC Power Fail Relay,
(N.O. Contact closes when ac line voltage is applied)
(N.O. Contact opens when ac line voltage is removed)
Littelfuse P/N 218005
Blade P/N 257015
(AC Hot, AC Neut & GND)
(Pos +, Neg -)
Form C, 2Amps, 12Vdc