Toshiba 1500 Series Operation Manual page 16

Hide thumbs Also See for 1500 Series:
Table of Contents

Advertisement

TOSHIBA
4.0
Specifications
4.1
Standard Series Specifications (Cont'd)
Input
Battery
Battery backup time when fully charged
with 0.7 power factor at77° F (25° C)
Output
Output voltage regulation
Output voltage waveform
Rated load power factor
Voltage transient characteristic
Rated output current (rms)
Maximum output current (peak)
Inverter overload capacity
Environment
Switches
Interfaces
Fault detect and input power loss
Options
Software for unattended
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
MODEL NUMBER
UE1A1A012C6
CAPACITY
1200 VA (0.84 kW)
Input voltage
Single phase, 120 Vac, +10% to -30% (*)
Input frequency
45 to 65 Hz
Input capacity
1200 VA
Input power factor
Approximate unity (0.95 to 1.0)
Battery rated voltage
60 Vdc
5 min. at full load (**)
12 min. at half load (**)
Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed lead-acid
Output voltage
Single-phase, 120 volts
Within +/- 3%, steady state
Output frequency
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
0.7 lagging (0.6 to 1.0)
+/- 8% under 100% load step change
10.0A
30.0A
150% for 30 seconds
Crest factor
3.0
Operating temperature
32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature
-4 to 104° F (-20 to 40° C)
Operating humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
External dimensions
8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight
43.7 lb (19.8 kg)
Acoustical noise
50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
87%
Bypass switch
Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
IBM (TM) AS/400
LAN Manager
See section 6.0 for details.
RS232 ASCII
computer shutdown
Contact Toshiba for details on this option
External battery pack
Contact Toshiba for details on this option
4 - 2