Specifications

Generator Set

Model
Rated voltage
Rated maximum load
current (a) at rated
voltage*
Main line circuit breaker
(generator set disconnect)
Phase
Rated AC frequency
Battery requirement
Enclosure
Weight (kg / lbs)
Normal operating range
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA-C22.2 No. 100-04
Standard for Motors and Generators.
* Natural gas ratings will depend on specific fuel BTU / joules content. Typical derates are between 10–20% of the LP gas rating.
** Circuits to be moved must be protected by same size breaker. For example, a 15A circuit in the main panel must be a 15A circuit in the transfer
switch.

Engine

Model
Engine type
Number of cylinders
Displacement
Cylinder block
Recommended spark plug
Spark plug gap
Valve clearance
Starter
Oil capacity including filter
Recommended oil filter
Recommended air filter
Engine power is subject to and limited by such factors as fuel BTU/joules, ambient temperature and altitude. Engine power decreases approxi-
mately 3.5% for each 304.8 m (1,000 ft) above sea level, and also will decrease approximately 1% for each 6 °C (10 °F) above 15 °C (60 °F) ambi-
ent temperature.
A detailed specification sheet for a particular generator set is available from an IASD.
Owner's Manual for Australian 3-Phase 50 Hz Air-Cooled Generator Sets
12V, Group 25R 540 CCA minimum, or Group 35 AGM 650 CCA minimum
This unit is tested in accordance to UL 2200 standards with an operating temperature of -29 °C (-20
°F) to 50 °C (122 °F). For areas where temperatures fall below 0 °C (32 °F), a cold weather kit is
recommended. There may be a decrease in engine power when operated above 25 °C (77 °F).
(Please reference the engine specifications section.)
20 kVA
380 / 400 / 416
30.4 / 28.9 / 27.18
32 A
3
50 Hz
(See
Replacement
Parts)
Aluminum
192.8 / 425
20 kVA
Generac G-Force 1000 Series
2
999 cc
Aluminum w/ cast iron sleeve
See
Replacement Parts
1.02 mm (0.040 in)
0.05–0.1 mm (0.002–0.004 in)
12 VDC
Approx. 1.8 L (1.9 qts)
See
Replacement Parts
See
Replacement Parts
General Information