Remote Ac Bus Synchronization - ABB SureWave SFC User Manual

Static frequency converter
Table of Contents

Advertisement

71/78
––

Remote AC bus Synchronization

The SureWave SFC can connect to a live AC bus using its in-built synchronizer. This allows unin-
terrupted power to an AC bus while transferring from alternate AC power sources such as
standby generators to the SFC.
The seamless transfer function is controlled by using the main controller digital I/O as described
in 9.2 I/O interfaces.
11.6.1 Transfer generator to SFC
11.6.1.1
Generator to SFC installation SLD
Control I/O
 Sync enable
 Droop enable
 Synchronized
Figure 11-2: Seamless transfer from a generator to SFC
The installation and connection of the SureWave SFC to allow seamless transfer from a genera-
tor is shown in Figure 11-2: Seamless transfer from a generator to SFC.
Note, for proper operation the phase and voltage relationship between the voltages measured
by the external voltage sense and the inverter terminals must be known. A neutral is not re-
quired for the synchronizing function and if present, does not need to be connected to the ex-
ternal voltage sense board.
11.6.1.2 Generator to SFC transfer procedure
The procedure for transferring from generator to SFC is as follows. Please refer to the SureWave
commissioning manual for a complete detailed transfer procedure description.
SUREWAVE SFC USER MANUAL
PEBBs
Main
GDM
Controller
SureWave SFC
Output Isolation
Transformer
3
Output CB
3
External Voltage
Sense Board
3
Generator CB
AC Bus
3

Advertisement

Table of Contents
loading