1135 SERIES WIRELESS SIREN
Installation Guide
DESCRIPTION
The 1135 Series Wireless Siren
provides up to 110 decibels of
annunciation. It includes a wall
tamper, a cover tamper, and a
Survey LED.
Multiple sirens can be activated
simultaneously by the panel using
the Trip with Panel Bell option. This
option allows the siren to follow the
panel bell output including the bell
cutoff time.
In addition to these features, the
1135E Wireless Siren communicates
with the panel using 128‑bit AES
encryption.
Compatibility
•
All DMP 1100 Series Wireless
Receivers and burglary panels
What is Included?
•
One 1135 Series Wireless Siren
•
Two 3.0 V Lithium CR123
Batteries
•
Hardware Pack
1
PROGRAM THE PANEL
To program the 1135 Series into the panel, select one of the
following methods: Choose Method 1 to make the siren a non‑
standard output that follows the panel bell or Method 2 to make
the siren a standard output.
A house code must be programmed in the panel's SYSTEM
OPTIONS before programming wireless devices. Range is 1 ‑ 50.
For 1135E encrypted sirens to communicate with the panel, 1100
ENCRYPTION must be enabled and a passphrase must be set in
SYSTEM OPTIONS programming.
To enter panel programming, reset the panel and enter 6653
(PROG) at a keypad. After completing each of the following
steps, press CMD to advance to the next prompt. After you finish
programming, go to STOP and press CMD to save and exit the
Programmer menu. For more information, refer to the appropriate
panel programming
PANEL MODEL
XR Series
XT Series
XTL Series
Table 1: Valid Output Numbers by Panel Model
Method 1: Non-Standard Output (Follow Panel)
1.
Go to OUTPUT INFO (XR Series) or OUTPUT SETUP
(XT and XTL Series).
At OUTPUT NO, enter the output number. Refer to
2.
3.
At OUTPUT NAME, enter a descriptive name for the siren.
4.
At SERIAL#, enter the 8‑digit device serial number.
5.
At SUPRVSN TIME, enter the supervision time in minutes.
Ensure TRIP WITH PANEL BELL is set to YES (default).
6.
Go to BELL OPTIONS and set the BELL CUTOFF. Range is
7.
1 ‑ 15 minutes.
Method 2: Standard Output (Standalone)
Go to OUTPUT INFO (XR Series) or OUTPUT SETUP
1.
(XT and XTL Series).
2.
At OUTPUT NO, enter the output number. Refer to
3.
At OUTPUT NAME, enter a descriptive name for the siren.
At SERIAL#, enter the 8‑digit device serial number.
4.
At SUPRVSN TIME, enter the supervision time in minutes.
5.
6.
At TRIP WITH PANEL BELL, select NO.
guide.
VALID OUTPUT NUMBERS
450‑474 (slow) or 480‑499 (fast)
31‑34 (slow) or 41‑44 (fast)
51‑54 (slow) or 61‑64 (fast)
Table
1.
Table
1.
Need help?
Do you have a question about the 135 Series and is the answer not in the manual?
Questions and answers