Specification - Viessmann VITOCAL 242-G Installation And Service Instructions Manual

Compact heat pumps
Hide thumbs Also See for VITOCAL 242-G:
Table of Contents

Advertisement

Specification

400 V appliances
Type BWT
Output data, heating to EN 14511 (B0/W35, 5 K
spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance
Output data, heating with reference to EN 255
(B0/W35, 10 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance
Brine (primary circuit)
Content
Minimum flow rate (must be maintained)
Max. external pressure drop (RFH) at minimum
flow rate
Max. flow temperature (brine inlet)
Min. flow temperature (brine inlet)
Heating water (secondary circuit)
Content, heat pump
Content, total
Minimum flow rate (must be maintained)
Max. external pressure drop (RFH) at minimum
flow rate
Max. flow temperature
Instantaneous heating water heater
Heating output
Rated voltage
MCB/fuse protection
Solar circuit
Content
Electrical values, heat pump
Rated voltage, compressor
Rated current, compressor
Starting current, compressor
(with starting current limiter, not for type
BWT 241.A06)
Starting current, compressor (with stalled arma-
ture)
MCB/fuse protection for compressor
Rated voltage, heat pump control unit/PCB
MCB/fuse, heat pump control unit/PCB (internal)
kW
kW
kW
(COP)
ε
kW
kW
kW
(COP)
ε
l
l/h
mbar
kPa
°C
°C
l
l
l/h
mbar
kPa
°C
kW
l
A
A
A
A
241.A06
241.A08
5.9
7.7
4.6
6.0
1.40
1.87
4.2
4.2
6.2
8.0
4.9
6.4
1.36
1.77
4.5
4.5
2.8
3.1
820
1120
680
630
68
63
15
15
5
5
3.3
3.5
6.2
6.4
600
710
580
580
58
58
60
60
8.8
3/N/PE 400 V/50 Hz
3 x B16A 1-pole
7.2
7.2
3/PE 400 V/50 Hz
5.5
6.0
25.0
14.0
26.0
35.0
1 x C16A
1 x B16A
3-pole
3-pole
1/N/PE 230 V/50 Hz
6.3 A (slow)/250 V
Specification
241.A10
10.0
7.8
2.35
4.3
10.4
8.3
2.23
4.6
3.4
1450
590
59
15
5
3.8
6.7
910
540
54
60
7.2
8.0
20.0
48.0
1 x B16A
3-pole
95

Advertisement

Table of Contents
loading

This manual is also suitable for:

754917375491747549175754917675491777549178

Table of Contents