Expansion Pcb On Main Pcb (230 V~ Components); Luster Terminals (Alarm And Safety Connections) - Viessmann VITOCAL 242-G Installation And Service Instructions Manual

Compact heat pumps
Hide thumbs Also See for VITOCAL 242-G:
Table of Contents

Advertisement

Installation sequence
Electrical connections
Connecting the temperature limiter, part no. 7151 728,
7151 729
B
to mixer extension kit
A
B
M
C
1~
Fig. 22
A
Connect plug
to mixer extension kit
Temperature limiter
B
Heating circuit pump for heating circuit with mixer
C

Expansion PCB on main PCB (230 V~ components)

Do not make any on-site connections.

Luster terminals (alarm and safety connections)

Set the required parameters during commissioning:
see page 43 onwards.
Terminals
Function
X3.1
Switched phase
X3.3
Flow switch
X3.4
X3.6
Power-OFF (factory-fitted jumper)
X3.7
G
26
(cont.)
Explanation
Via control unit ON/OFF switch
Note
Observe the total load 1000 W of all connected compo-
nents.
Requires floating N/O contact:
Closed: Heat pump in operation
Open: Heat pump shut down
Breaking capacity 230 V, 0.15 A
Remove jumper when connecting.
Requires floating N/C contact:
Closed: Heat pump in operation
Open: Heat pump shut down
Breaking capacity 230 V, 0.15 A
Remove jumper when connecting.