Huawei UPS5000-H User Manual page 364

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Procedure
Step 1 On the WebUI, choose Monitoring > UPS System > Running Parameter >
System Settings, and set Paral sys hibernate to Enable.
Step 2 Set Module cycle hiber period(d) to an integer ranging from 1 to 100. The
default value is 30.
Figure 7-27 System settings
----End
Issue 05 (2021-10-13)
NO TE
Click Submit after setting parameters on the WebUI.
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
354