Connecting the DCS and NRI to the NPM
In X-618 system, DCS, NRI and NPM form a complete system through the Ethernet.
The DCS and NRI can be connected to the NPM in the following two ways:
Directly connecting the DCS and NRI to the NPM
Connecting the DCS and NRI to the NPM through a network switch
Directly Connecting the DCS and NRI to the NPM
Use twisted pair cables to connect the network ports of DCS, NRI and NPM.
Following are the steps:
Insert one end of the prepared twisted-pair cable into the network port located on the rear panel of
the DCS, and the other end of the cable into the RJ45 port located on the rear panel of the X-
NPMS, and connect the network port of DCS to the NRI's network port using another twisted-pair
cable.
Connecting the DCS and NRI to the NPM through a Network Switch
Connect the DCS and NRI to the NPM through a network switch. The DCS and network switch
must be on the same network.
Connecting the Power Supply Cables
The power supply cables for the main X-618 system components include the following items:
Connecting DCS and NRI Main and Standby Power Supply Cables
Connecting DA Main and Standby Power Supply Cables
Connecting NPM Power Supply Cable
Connecting DCS and NRI Main and Standby Power Supply Cables
Connecting AC Power Supply Cables
The AC power interfaces of X-NRI use phoenix sockets. Generally, the main power supply cables
are equipped when leaving the factory, but manually connecting AC power to the device also
needed under some circumstances. Here are the steps:
1.
Strip off the wire jacket of one end of the AC power supply cable by 20mm and connect the
cable to the main power supply wiring terminal.
Figure 22 Schematic Diagram of Connection of AC Power Supply Cables
19