12 Specific data IO-Link (pin 6)
12.4.35 Set value (W) input
The function of the analog input can be set with the Set value (W) input parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0xB8
1
0
R/W
2
8
R/W
3
16
R/W
4
24
R/W
5
32
R/W
Description of parameter values
Index name
Set value (W) input
GEMÜ R563 eSyStep
Length
Index name
1 bit Set value (W) input
2 bits
8 bits
8 bits
8 bits
Parameter
Values
Direction
Type
I min
0 to 40
(0 to 4.0 mA)
I max
200 to 220
(20.0 to 22.0
mA)
U max
100 to 110
(10.0 to 11.0 V)
Parameter
Type
Direction
uint:1
Type
uint:2
I min
uint:8
I max
uint:8
U max
uint:8
0
Specify direction of the set value input.
1
0 = Rise (rising)
1 = Fall (falling)
0
Determine signal input.
1
0 = 0 to 20 mA
2
1 = 4 to 20 mA
2 = 0 to 10 V
Determine minimum value of the current input. If the set
value is not reached, the message "Set value too small" is is-
sued.
Determine maximum value of the current input. If the set
value is exceeded, the message "Set value too high" is is-
sued.
Determine maximum value of the voltage input. If the set
value is exceeded, the message "Set value too high" is is-
sued.
44 / 54
Default
Values
0
0
1
1
0
1
2
35
0 to 40
(0 to 4.0 mA)
205
200 to 220
(20.0 to 22.0 mA)
103
100 to 110
(10.0 to 11.0 V)
Description