GEM eSyStep R563 Operating Instructions Manual page 12

Motorized control valve
Hide thumbs Also See for eSyStep R563:
Table of Contents

Advertisement

7 Technical data
7.7 Electrical data
Supply voltage Uv:
Rating:
Operation:
Reverse battery protec-
tion:
▶ The specified characteristics and values apply to the factory setting.
▶ With reduced forces, higher duty cycles and/or higher ambient temperatures are possible. At higher force settings the duty
cycle and/or ambient temperature is reduced.
▶ IO-Link: Index 0x90 - Subindex 2 - Force
7.7.1 Analogue input signals – Control module Positioner (code S0, S5, S6)
7.7.1.1 Set value
Input signal:
Input type:
Input resistance:
Accuracy/linearity:
Temperature drift:
Resolution:
Reverse battery protec-
tion:
7.7.2 Digital input signals
Inputs:
Input voltage:
Logic level "1":
Logic level "0":
Input current:
7.7.3 Analogue output signals – Control module Positioner (code S0, S5, S6)
7.7.3.1 Actual value
Output signal:
Output type:
Accuracy:
Temperature drift:
Load resistor:
GEMÜ R563 eSyStep
24 V DC ± 10%
Actuator size 0 (code 0A)
Stepper motor, self-locking
Yes
0/4 - 20 mA; 0 - 10 V (function selectable via IO-Link)
passive
250 Ω
≤ ±0.3% of full flow
≤ ±0.1% / 10°K
12 bit
Yes (up to ± 24 V DC)
Function selectable via IO-Link (see table Overview of available functions – Input and output sig-
nals)
24 V DC
> 15.3 V DC
< 5.8 V DC
typically < 0.5 mA
0/4 - 20 mA; 0 - 10 V (function selectable via IO-Link)
active
≤ ±1% of full flow
≤ ±0.1% / 10°K
≤ 750 kΩ
20 W
NOTICE
12 / 54
www.gemu-group.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

R563 esystep

Table of Contents