Pull Down Function; Defrost Operations; Timed Or Temperature Controlled Mode; Evaporator Fan - Emerson DIXELL XR30T Installing And Operating Instructions

Full touch
Table of Contents

Advertisement

Energy
Normal
Saving
mode
NOTE: the cycling mode (ES - Normal mode - ES - etc.) works if i1F=dor, EtS and StE are different from
zero. If EtS=0 or StE=0, the controller will not change the operating mode, and it will be possible to change
from the normal mode to the energy saving mode by using the ES button or by setting i1F=ES.

8. PULL DOWN FUNCTION

The Pull Down is automatically activated:
After any defrost cycle
After power-on if T>SET+CCS
When the regulation probe temperature T is:
T>SET+HY+oHt value in normal mode
o
T>SET+HES+HYE+oHE value in energy saving mode
o
In these cases, a different set-point value (SET+CCS) will be used. As soon as the room temperature
reaches the SET+CCS value, the compressor will stop and the normal regulation will restart.
NOTE:
Pull Down function is disabled when CCS=0 or CCt=0.
The CCt parameter sets the maximum activation time for any pull down. When CCt expires, the Pull
Down will be immediately stopped and the standard SET-POINT will be restored

9. DEFROST OPERATIONS

Any defrost operation can be controlled in the following way:
EdF=rtC: by using an internal real-time clock (only for models equipped with RTC)
EdF=in: timed defrost, in this case a new defrost will start as soon as the idF timer elapses
9.1

TIMED OR TEMPERATURE CONTROLLED MODE

Two defrost modes are available: timed or controlled by a temperature probe. A couple of parameters are
required to control intervals between defrost cycles (idF) and maximum duration (MdF). During a defrost
cycle it is possible to select some different visualizations by using the par. dFd. Available defrost types are:
tdF=EL: with an electric heater
tdF=in: by using hot gas cycle

10. EVAPORATOR FAN

To enable the evaporator fan management, setting set an evaporator probe is required (par. FAP). Here are
the involved parameters:
FAP: to select the control probe
FSt: to select the deactivation set point
HYF: differential
FnC: to define the working mode:
C-n: in parallel with compressor output and stopped during any defrost. When compressor is OFF,
o
they will start a duty-cycle mode (see FoF, Fon, FF1 and Fo1 parameters)
O-n: always on, stopped during any defrost
o
C-Y: in parallel with compressor output and always on during any defrost. When compressor is
o
OFF, they will start a duty-cycle mode (see FoF, Fon, FF1 and Fo1 parameters)
o-Y: always on
o
Fnd: activation delay after any defrost

10.1 EVAPORATOR FAN AND DIGITAL INPUT

When a digital input is configured as a door switch (i1F or i2F=dor) and this digital input is active, evaporator
fan and compressor status will depend on par. odC:
odC=no: normal regulation
odC=FAn: evaporator fan OFF
odC=CPr: compressor OFF
1592040000 XR30-60-70T EN v1.3 2020.08.26
Activate the ECO function from Virtual Keyboard screen.
Controller in ES mode for time EtS.
If the controller is in ES mode, it returns in Standard mode when the door
stays open more than time dS.
XR30-60-70T
32/40