4.7

SETPOINT MENU

When in Programming Menu, it is possible to enter the Setpoint Menu by touching the SET icon for 3 sec.
Both SET and PRG icons will blink until the Setpoint Menu is unlocked. Both PROG LEVEL icons start
toggling to indicate that the visualized value is editable. Press the BACK icon to exit (come back to the
Programming Menu) without saving.
4.8
HOTKEY – UPLOAD
When in Programming Menu, it is possible to activate the HotKey Upload Menu function to save the
current device configuration (parameter values) into the external memory. To do this, follow these
instructions:
1. H-swipe to go on the UPL screen
2. Insert the HotKey (on the 5-pin ports on the back of the device)
3. Touch the PRG icon for 3 sec
4. The copying procedure will start and the PRG icon will blink during the copy operations
5. At the end of the copying procedure, a message will notify the user that the operation has been
competed successfully:
a. End: all parameters have been copied
b. Err: some error occours during copying operations
4.9
HOTKEY – DOWNLOAD
When in Power-off or in Stand-by mode, it is possible to activate the HotKey Download Menu function to
copy a new configuration (parameter values) into the current device memory. To do this, follow these
instructions:
1. Insert the HotKey (on the 5-pin ports on the back of the device)
2. Touch the OFF icon for 3 sec
3. After power-on, the copying procedure will start automatically and the PRG icon will blink during the
copy operations
4. At the end of the copying procedure, a message will notify the user that the operation has been
competed successfully:
a. End: all parameters have been copied
b. Err: some error occours during copying operations
4.10 X9
Every parameter is normally identified by a unique label that can have two or three alphanumeric characters.
When in the "X9" Screen, it is possible to create the parameter label by swiping-up every single part of the
label itself (first, second and third char). The system is able to drive the user through the available symbols,
showing only the available ones to speed up the creation of the label.
For example, if a modification of the "interval between defrosts" parameters is required (label "idF"), these
are the steps to follow:
-
Enter the X9 screen
-
Swipe-up or down the first char position (lower segment on the left) until char "i" (lowercase) appears
1592040000 XR30-60-70T EN v1.3 2020.08.26
XR30-60-70T
11/40