Evaporator fan ON time in energy saving mode (with compressor OFF) (0 to 255 min) used
Fo1
when energy saving status is active.
Evaporator fan OFF time in energy saving mode (with compressor OFF): (0 to 255 min) used
FF1
when energy saving status is active.
Fd1
Evaporator fan delay: (0 to 255 sec) delay before activating evaporator fan
Evaporator fan delay after closing door: (0 to 255 sec) delay before activating evaporator fan
Fd2
and after closing the door
Probe selection for condenser fan: (nP; P1; P2; P3; P4) nP=no probe; Px=probe "x". Note:
FAC
P4=Probe on Hot Key plug.
Set Point 2 regulation (for condenser fan): (-55 to 50°C; -67 to 122°F) setting of temperature
St2
detected by evaporator probe. Above this value of temperature fans are always OFF.
Set Point 2 differential (for condenser fan): (0.1 to 25.5°C; 1 to 45°F) differential for evaporator
HY2
ventilator regulator
Condenser fan operating mode: (Cn; on; CY; oY)
Cn = runs with the compressor and OFF during defrost
FCC
on = continuous mode, OFF during defrost
CY = runs with the compressor and ON during defrost
oY = continuous mode, ON during defrost
Fd3
Condenser fan activation delay: (0 to 255 sec) delay before activating condenser fan
Fd4
Condenser fan deactivation delay: (0 to 255 sec) delay before deactivating condenser fan

5.1.6 Auxiliary regulator parameters - AUS

ACH
Type of control for auxiliary regulator: (Ht; CL) Ht = heating; CL = cooling.
Set Point for auxiliary regulator: (-55.0 to 150.0°C; -67 to 302°F) it defines the room temperature
SAA
set point to switch auxiliary relay.
Auxiliary regulator differential: (0.1 to 25.5°C; 1 to 45°F) differential for auxiliary output set point.
SHY
ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA.
ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out is SAA.
Probe selection for auxiliary regulator: (nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay is
ArP
switched only by the digital input; Px=probe "x". Note: P4=Probe on Hot Key plug.
Auxiliary regulator disabled during any defrost cycle: (n; Y) n = the auxiliary relay operates
Sdd
during defrost. Y = the auxiliary relay is switched off during defrost.
Base time for parameters Ato and AtF: (SEC; Min) SEC = base time is in second; Min = base
btA
time is in minutes.
Ato
Interval of time with auxiliary output ON: 0 to 255 (base time defined in par. btA)
AtF
Interval of time with auxiliary output OFF: 0 to 255 (base time defined in par. btA)

5.1.7 Alarm configuration parameters

Probe selection for temperature alarms: (nP; P1; P2; P3; P4) nP=no probe; Px=probe "x". Note:
ALP
P4=Probe on Hot Key plug.
ALC
Temperature alarms configuration: (Ab, rE) Ab = absolute; rE = relative.
High temperature alarm: when this temperature is reached, the alarm is enabled after the Ad
delay time.
ALU
If ALC=Ab → ALL to 150.0°C or ALL to 302°F.
If ALC=rE → 0.0 to 50.0°C or 0 to 90°F.
Low temperature alarm: when this temperature is reached, the alarm is enabled after the Ad
delay time.
ALL
If ALC=Ab → -55.0°C to ALU or -67°F to ALU.
If ALC=rE → 0.0 to 50.0°C or 0 to 90°F.
AFH
Temperature alarm differential: (0.1 to 25.0°C; 1 to 45°F) alarm differential.
Temperature alarm delay: (0 to 255 min) delay time between the detection of an alarm condition
ALd
and the relative alarm signalling.
Temperature alarm delay when door open: (0.0 to 24h00min, res. 10 min) delay time between
dot
the detection of a temperature alarm condition and the relative alarm signalling, after starting up the
instrument.
Temperature alarm delay at start-up: (0.0 to 24h00min, res. 10 min) delay time between the
dAo
detection of a temperature alarm condition and the relative alarm signalling, after starting up the
instrument.
Probe selection for second temperature alarm: (nP; P1; P2; P3; P4) nP=no probe; Px=probe
AP2
"x". Note: P4=Probe on Hot Key plug.
1592040000 XR70T EN v1.1 2019.07.09