Wallbox PULSAR PLUS Installation Manual page 8

Hide thumbs Also See for PULSAR PLUS:
Table of Contents

Advertisement

Available languages

Available languages

EN
INSTALLATION
Hardwired Installation
L1
L2
Hot wires
Ground
Black + Red
Green or
Bare wire
14
Mounting the charger
1.
Carefully remove your charger from the
packaging box and hang it from the top of the
wallplate.
For rear wiring installation, feed the power supply
wires through the rear port (and through the rubber
grommet, if not using conduit) with enough length
to easily connect the wires to the terminals.
2.
Replace the two wallplate screws to secure
your charger to the wallplate. Do not over-tighten.
x2
ø3.5 x 9.5mm
Electrical wiring
1.
For bottom wiring installation, feed the power
supply wires through the bottom port with enough
length to easily connect the wires to the terminals.
NOTE: If using a conduit connection, pull the
wiring through before connecting the conduit.
2.
Connect the electrical wires according to the
diagram on the left.
Ensure the electrical panel supports a 208/240V
dedicated circuit with a new, dedicated two-pole
circuit breaker, rated for the selected amperage
(see following section). The voltage between the
hot wires (L1 and L2) must be 208/240V.
3.
Use copper conductors only within the wire
size range of 10 to 6 AWG (6mm2 to 16mm2).
4.
Strip 1/2" (12mm) of insulation off each wire,
insert the wires per the diagram, and tighten each
connector screw to 11.5in·lbs (1.3N·m)
INSTALLATION
Hardwired Installation
The 40A and 48A
versions are set to
position 7 by default.
Current
selector
Selecting a switch position
exceeding the rated current will
not exceed the rated current.
CAUTION To reduce the risk of fire, only connect
your charger to a circuit with a branch circuit
overcurrent protection of 125% of the selected max
amperage setting of the device in accordance with
ANSI/NFPA 70 (US) C22.2 NO 280 13 (Canada).
Amperage Reduction Label
PULSAR PLUS
SN: 123456
Wallbox Chargers S.L.
UID: abcdefgh
08/2020 Made in Spain
22ºF to 104ºF (-30ºC to 40ºC)
PN: PUP1-U-1-5-N-002-A
20A
Enclosure Type 3R
Input/Output:
208/240VAC, 60Hz, 48A
Input/Output:
Input/Output:
EV Charger
20A
208/240VAC, 60Hz, 16A
208/240VAC, 60Hz, 16A
Input/Output:
Input/Output:
EV Charger
25A
208/240VAC, 60Hz, 20A
208/240VAC, 60Hz, 20A
Input/Output:
Input/Output:
EV Charger
208/240VAC, 60Hz, 24A
208/240VAC, 60Hz, 24A
30A
EV Charger
208/240VAC, 60Hz, 32A
Input/Output:
208/240VAC, 60Hz, 32A
Input/Output:
40A
Input/Output:
Input/Output:
50A
EV Charger
208/240VAC, 60Hz,40A
208/240VAC, 60Hz, 40A
Save this label sheet for future use.
Torque: 13.3in·lbs (1.5N·m)
Rated current adjustment
1.
Both the 40A and 48A versions of Pulsar Plus
can be adjusted from 16A to the maximum rated
amperage of each model. If you are installing your
charger on a circuit rated lower than the maximum
rating for your charger, you can use the current
selector to manually set a lower maximum current.
Hardwire installations
2.
On your charger cover, locate the current
selector and set the rotary switch to the
appropriate setting per the chart below.
Position
Amps
Circuit Breaker Rating
2
16A
20A
3
20A
25A
4
24A
30A
5
32A
40A
6
40A
50A
7
48A
60A
3.
When setting your charger's current lower
than the max.rating, use the label corresponding
to your selected current value from the enclosed
amperage reduction label sheet and affix it over
the existing label on your charger.
Closing the charger
1.
Carefully reattach the communications cable
to your charger cover and close the cover of your
charger.
2.
Insert the four corner screws to secure your
charger cover. Do not over-tighten.
3.
Making sure to properly align the bottom
screw opening, place the cover frame on your
charger and attach the frame with the screw.
Do not over-tighten.
ø T20
5 x 10mm
Proceed to the instructions for installing the
holster and operating your charger, pages 16-17.
15
EN