G
®
AERASGARD
KLQ - SD / KLQ - W
Patented quality product (patent no. DE 10 2014 010 719.1)
Maintenance-free duct sensor AERASGARD
for determining the air quality in three VOC sensitivity levels (low/medium/high). The measuring transducer converts the measured values into a
standard signal of 0 -10 V.
Maintenance-free duct sensor AERASGARD
housing with quick-locking screws, for determining the air quality in three VOC sensitivity levels (low/medium/high). The measuring transducer
converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the loading of the room air
due to contaminated gases such as cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions from building components,
etc. With regard to the expected air contamination, low, medium or high VOC sensitivity can be selected.

TECHNICAL DATA

Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Service life:
Gas exchange:
Warm-up time:
Response time:
Ambient temperature:
Electrical connection:
Housing:
Housing dimensions:
Cable connection:
Protective tube:
Process connection:
Protection class:
Protection type:
Standards:
®
KLQ-SD with active output, automatic calibration (fixed), in a compact plastic housing with snap-on lid,
®
KLQ-W with active/switching output, automatic calibration (can be deactivated), in a compact plastic
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
VOC sensor (metal oxide) (VOC = volatile organic compounds),
with manual calibration (via zero button),
KLQ - SD
with automatic calibration (fixed)
KLQ -W
with automatic calibration (can be deactivated via DIP switches)
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensibility low, medium, high
(0 V = clean air, 10 V = polluted air)
KLQ - SD
0 -10 V (fixed)
KLQ - W
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches), with offset potentiometer (± 10 % of the measuring range)
KLQ - SD
without changeover contact
KLQ - W
with potential-free changeover contact (24 V / 1 A), switchpoint adjustable
± 20 % of final value (referred to calibrating gas)
> 60 months (under normal load conditions),
depending on the type of loading and gas concentration
by diffusion
approx. 1 hour
approx. 1 minute, minimum flow rate 0.3 m / s (air)
–10...+60 °C
0.14 - 1.5 mm
2
, via terminals
plastic, UV-stabilised, material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016),
KLQ - SD
with snap-on lid,
KLQ -W
with quick-locking screws (slotted ⁄ Phillips head combination)
72 x 64 x 37.8 mm (Tyr 1/Tyr 01 without display)
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
TM
PLEUROFORM
, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, v
by mounting flange, plastic (included in the scope of delivery)
III (according to EN 60 730)
KLQ - SD
IP 54 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)
KLQ - W
IP 65 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
* Housing in the built-in state (permeable PLEUROFORM: IP 30)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
= 30 m/s (air)
max
Rev. 2020 - V34