2.4 Connecting the Failsafe Alarm Relay
To mount the device to a panel, do the following:
1.
2.
2.4

Connecting the Failsafe Alarm Relay

The failsafe relay can be configured to latch based on alarm conditions. The NO
(Normally Open) contact is closed when the unit is powered and there are no ac-
tive alarms. If the device is not powered or if an active alarm is configured, the relay
opens the NO contact and closes the NC (Normally Closed) contact.
Note
Control of the failsafe relay output is configurable through RUGGEDCOM RSG2200F .
One common application for this relay is to signal an alarm if a power failure oc-
curs. For more information, refer to the RUGGEDCOM RSG2200F User Guide for the
RUGGEDCOM RSG2200F.
The following shows the proper relay connections.