In case of V3 models
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07
1 Power supply cable:
▪ Use the factory-mounted cable, which is already routed through the frame.
▪ Connect the wires to the terminal block.
▪ Fix the cable with a cable tie.
Use the factory-mounted cable.
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
b
L
a
N
b
L
1N~,
50 Hz,
N
230 V AC
a Factory-mounted power supply cable
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2 pole, 32 A fuse, C curve.
Q1DI Earth leakage circuit breaker (30 mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block (make sure the numbers match with
the numbers on the indoor unit) and the earth screw.
▪ Fix the cable with a cable tie.
Wires: (3+GND)×1.5 mm²
L N PE
F1B
Q1DI
BRN
2
1
BLU
4
3
YLW/GRN
8
Electrical installation
|
a
Installer reference guide
93