To Connect The Main Power Supply - Daikin Altherma 3 H HT F Series Installer's Reference Manual

Hide thumbs Also See for Altherma 3 H HT F Series:
Table of Contents

Advertisement

8.3.1 To connect the main power supply

EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07
Item
Human Comfort Interface
LAN adapter
LAN adapter – System requirements
The requirements posed on the Daikin Altherma system depend on the LAN
adapter application/system layout (app control, or Smart Grid application).
App control:
Item
LAN adapter software
Unit control method
Smart Grid application:
Item
LAN adapter software
Unit control method
Domestic hot water
settings
Power consumption
control settings
1 Open the following (see
Description
See:
Installation and operation manual of the
Human Comfort Interface
Addendum book for optional equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9] Control
[1.6] Room sensor offset
See:
Installation manual of the LAN adapter
Addendum book for optional equipment
Wires: 2×(0.75~1.25 mm²). Must be
sheathed.
Maximum length: 200 m
See below ("LAN adapter – System
requirements").
Requirement
It is recommended to ALWAYS keep the LAN adapter
software up-to-date.
On the user interface, make sure to set [2.9]=2
(Control = Room thermostat)
Requirement
It is recommended to ALWAYS keep the LAN adapter
software up-to-date.
On the user interface, make sure to set [2.9]=2
(Control = Room thermostat)
To allow for energy buffering in the domestic hot
water tank, on the user interface, make sure to set
[9.2.1]=4 (Domestic hot water = Integrated).
On the user interface, make sure to set:
[9.9.1]=1 (Power
Continuous)
[9.9.2]=1 (Type = kW)
"6.2.5 To open the indoor
8
Electrical installation
|
control =
consumption
4
unit" [
 61]):
Installer reference guide
101