Configuration

9.5.2 Room

Installer reference guide
136
Overview
The following items are listed in the submenu:
1
Operation
Malfunctioning

Room

Main zone
Additional zone
Setpoint screen
Control the room temperature of the main zone via setpoint screen [1] Room.
See
"9.3.5 Setpoint
screen" [
Schedule
Indicate if the room temperature is controlled according to a schedule or not.
#
Code
[1.1]
N/A
Heating schedule
Applicable for all models.
Define a heating schedule of the room temperature in [1.2] Heating schedule .
See
"9.3.7 Schedule screen:
Cooling schedule
Only applicable for reversible models.
Define a cooling schedule of the room temperature in [1.3] Cooling schedule.
See
"9.3.7 Schedule screen:
Antifrost
[1.4] Antifrost prevents the room from getting too cold. This setting is
applicable when [2.9] Control=Room thermostat, but also offers functionality
for leaving water temperature control and external room thermostat control. In
case of the latter two, Antifrost can be activated by setting field setting
[2-06]=1.
Room frost protection, when enabled, is not guaranteed when there is no room
thermostat that can activate the heat pump. This is the case when:
[2.9] Control=External room thermostat and [C.2] Space heating/
cooling=Off, or if
[1] Room
Setpoint screen
[1.1] Schedule
[1.2] Heating schedule
[1.3] Cooling schedule
[1.4] Antifrost
[1.5] Setpoint range
[1.6] Room sensor offset
[1.7] Room sensor offset
4
 125].
Schedule
No: Room temperature is directly controlled by
the user.
Yes: Room temperature is controlled by a
schedule and can be modified by the user.
4
Example" [
 126].
4
Example" [
 126].
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Description
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07