9
|
Configuration
Power consumption control
Installer reference guide
184
#
Code
[9.8.2]
[D-00]
[9.8.3]
[D-05]
Do NOT use 1 or 3. Setting [D-00] to 1 or 3 when [D-01] is set to 1 or 2 will reset
[D-00] back to 0, as the system does not have a booster heater. Only set [D-00] to
the values in the table below:
[D‑00]
0
2
Power consumption control
See
"5  Application guidelines" 
functionality.
#
[9.9.1]
[4-08]
[9.9.2]
[4-09]
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
Allow heater: Which heaters are allowed to
operate during preferential kWh rate power
supply?
0 No: None
1 Only BSH: Booster heater only
2 Only BUH: Backup heater only
3 All: All heaters
See table below.
Setting 2 is only meaningful if the preferential
kWh rate power supply is of type 1 or indoor unit
is connected to a normal kWh rate power supply
(via X2M/5‑6) and the backup heater is NOT
connected to the preferential kWh rate power
supply.
Allow pump:
0 No: Pump is forced off
1 Yes: No limitation
Backup heater
Forced OFF
Allowed
4
[
  27] for detailed information about this
Code
Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Description
Compressor
Forced OFF
Description
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07