Combination: Underfloor heating + Heat pump convectors
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the heat  pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
Benefits
Cooling. The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink function.
Stylish.
Space heating is provided by:
-
The underfloor heating
-
The heat pump convectors
Space cooling is provided by the heat  pump convectors only. The underfloor
heating is shut off by the shut-off valve.
Setup
A Main leaving water temperature zone
B One single room
a Heat pump convectors (+ controllers)
5
Application guidelines
|
Value
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
B
A
M1
a
Installer reference guide