5.5.2 Consumed energy

5.5.3 Normal kWh rate power supply

EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07
Setup and configuration: No additional equipment needed.
You can use the following methods to determine the consumed energy:
Calculating
Measuring
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater)
and measuring the consumed energy (example: for outdoor unit). If you do so, the
energy data will be invalid.
Calculating the consumed energy
The consumed energy is calculated internally based on:
-
The actual power input of the outdoor unit
-
The set capacity of the backup heater
-
The voltage
Setup and configuration: To get accurate energy data, measure the capacity
(resistance measurement) and set the capacity via the user interface for the
backup heater (step 1).
Measuring the consumed energy
Preferred method because of higher accuracy.
Requires external power meters.
Setup and configuration: When using electrical power meters, set the number of
pulses/kWh for each power meter via the user interface.
INFORMATION
When measuring the electrical power consumption, make sure ALL power input of
the system is covered by the electrical power meters.
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/5 and X5M/6. See
4
electricity
meters" [
 107].
Power meter type
In case of...
Single-phase outdoor unit
Backup heater supplied from a single-
phase grid (i.e. the backup heater
model is *3V or *6V connected to a
single-phase grid)
5
Application guidelines
|
"8.3.4  To connect the
Use a... power meter
Single-phase
(*3V, *6V (6V): 1N~ 230 V)
Installer reference guide
47