30/93
Building Technologies Division
Infrastructure & Cities Sector
5.4.2 Setpoint changeover SP1 / external setpoint via InP2
See chapter 8.3 Analog input InP3
See chapter 5.5. Weather-compensated
setpoint shifting
See chapter 7 Parameterization PArA
InP3
Function
:
See chapter 8.3 Analog input
FnC3 = 0 no function
Function of binary input D1:
binI = 2
Setpoint changeover:
Beschaltung binary input D1:
See chapter 4.3 Assignment of terminals
Figure 13: Setpoint changeover SP1 / external setpoint
User Manual RWF55...
5 Operating modes
InP3 (outside temperature)
Heating curve
At1
Factory setting:
= -10,
Ht1
At2
Ht2
= 60,
= 20,
InP3
0
1
Function
2
0
1
binI = 1
SPH oLHi
/
SPL oLLo
/
Active setpoint
= 50
InP2 FnC2
:
= 1
binI = 0 / 3
CC1U7867en
05.11.2013