Siemens RWF55.5 User Manual page 20

Compact universal controllers
Table of Contents

Advertisement

InP1
(actual value)
Analog input
Thermal element
Resistance thermometer in 3-wire circuit
Resistance thermometer in 2-wire circuit
0...135 Ω
Current input
DC 0...20 mA, 4...20 mA
Voltage input
DC 0...5 V, DC 1...5 V, DC 0...10 V
InP2
(external setpoint or setpoint
Analog input
shifting)
Resistance thermometer in 2-wire circuit
0...1000 
Current input
DC 0...20 mA, 4...20 mA
Voltage input
DC 0...5 V, 1...5 V, 0...10 V
InP3
(outside temperature)
Analog input
Resistance thermometer in 2-wire circuit
20/93
Building Technologies Division
Infrastructure & Cities Sector
Terminal no.
12
14
11
12
14
11
14
12 +
14 -
13 +
14 -
Terminal no.
21
23
21 +
23 -
22 +
23 -
Terminal no.
31
32
User Manual RWF55...
4 Electrical connections
Connection diagram
+12
-14
7867a13/0612
12
Ix
14
7867a06/0612
13
Ux
14
7867a07/0612
Connection diagram
21
23
7867a14/0612
21
Ix
23
7867a23/0612
22
Ux
23
7867a16/0612
Connection diagram
31
32
7867a17/0612
CC1U7867en
05.11.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rwf55.6Rwf55.50a9Rwf55.51a9Rwf55.60a9Rwf55.61a9

Table of Contents