Omega i Series User Manual page 57

Temperature & process controller
Hide thumbs Also See for i Series:
Table of Contents

Advertisement

ALARM 2 DISPLAY COLOR SUBMENU:
Press d
Press b
Press d
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the Display to change color every time when both Alarm 1
and Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Example 1:
Output 1 & Alarm 2: SSR
Alarm Setup: Absolute, Above, Alarm 2 HI Value "ALR.H" = 200, Alarm 1
HI Value "ALR.H" = 400
Color Display Setup: Normal Color "N.CLR" = Green, Alarm 1 Color
"1.CLR" = Amber, Alarm 2 Color "2.CLR" = Red
Display Colors change sequences:
GREEN
• -- ® ------------------------------ • ----------------------------- • ------------------------------ ®
0
Example 2:
Output 1 & Alarm 2: Pulse
Alarm Setup: Absolute, Below, Alarm 2 Low Value "ALR.L" = 300, Alarm 1
Low Value "ALR.L" = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER
• -------------- • ---------------------------------- • ------------------------------------------- -- •
0
AL1.L = 100
11) Display flashes previous selection for "Alarm 2 Color Display".
12) Scroll through the available selections: GRN , RED or AMBR .
13) Display shows STRD stored message momentarily and then
momentarily shows the software version number, followed by
RST Reset, and then proceeds to the Run Mode.
AL2.H = 200
RED
RED
AL1.H = 400
AL2.L = 300
53
AMBER
GREEN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cni8aCni16a

Table of Contents