CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Option 2: Select 'Erase Loop 1 device data first? Yes'
CAUTION: USING THIS OPTION WILL COMPLETELY ERASE THE PANEL'S DATABASE OF
STORED LOOP DEVICE INFORMATION EXCLUDING DEVICE ADDRESSES PREVIOUSLY
ASSIGNED BY A CAPROG PROGRAMMER, WHICH IS RETAINED. THIS IS DIFFERENT TO
THE AUTO ADDRESS FUNCTION. USE THIS OPTION WITH EXTREME CARE
Use this option if the panel has not previously been programmed, or if you want to program an existing system
as if it were a new system.
button to select 'Yes' then press the Accept
Press the scroll
The following message will appear:
Are you sure you want to erase
the Database? No
Only if you are confident to proceed, press the scroll
The panel will erase its database, update its flash memory and start a loop learn.
Wait for the process to complete and a summary window will appear, similar to the one shown below:
112 devices found
Auto learn complete, Press Accept
 button then press Escape button x 3 to return the panel to a normal condition.
Press the Accept
When requested by the panel remove the NVM link shown below:
AFTER A SUCCESSFUL LOOP LEARN YOU WILL HAVE A 'ONE OUT, ALL OUT' FIRE ALARM SYSTEM.
See Table 1 (page 6) for the default device assignment following a loop learn.
Page 8 of 16  Commissioning/Programming Quick Start Guide  Approved Document No. DFU5020010 Rev 4
 button shown below:
button to select 'Yes', then press the Accept
.
 button.