CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL
4.6.3 Assign a Sounder/VAD to a Group
A Group comprises of loop sounder/VADs and the panel's conventional sounders.
In the Loop Summary window, for each sounder/VAD, click on the drop-down menu in the
Zone/Group/Set column to assign a device to a Group (see FIG.5).
Note: In order to make any changes to the Zone/Group/Set data in the Loop Summary window,
click on the Enable Type/Zone Changes box.
There are a maximum of 16 Groups (which cannot be re-named), see
FIG.5 – Loop Summary Window
Normally, after a 'One Out, All Out' auto address or loop learn the I/O unit inputs are assigned to
Zone 1 and I/O units outputs to Set 1. If required, click on the 'Click for I/O Configuration' in the
Zone/Group/Set column to configure the I/O unit. See Table 1 (page 6) for default device
assignment.
Commissioning/Programming Quick Start Guide Approved Document No. DFU5020010 Rev 4 Page 13 of 16
'Edit Group
Configuration'.