CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL

4.9 Save Data from the PC Laptop to the Panel

After the site details have been entered, save the completed 'config data file' to the PC laptop.
Using the XFP Programming Tools, save the 'config data file' from the PC laptop to the
panel by clicking on the toolbar icon (shown right).
When requested by the panel fit the NVM link shown below:
Please fit the NVM Link now
or press ESCape to abort
The following message will appear at the panel:
Wait for the data transfer to complete.
Press Escape  button.
The panel will update its flash database.
ress Escape  button x 2.
P
When requested by the panel remove the NVM link shown below:
AFTER SAVING THE DATA TO THE PANEL, YOU WILL HAVE A NAMED,
ZONED, 'ONE OUT, ALL OUT' FIRE ALARM SYSTEM.
Page 16 of 16  Commissioning/Programming Quick Start Guide  Approved Document No. DFU5020010 Rev 4