Enter Site Details - C-TEC CAST XFP Commissioning & Programming Quick Start Manual

Analogue addressable fire alarm control panel, 1/2 loop, 16/32 zone panel
Hide thumbs Also See for CAST XFP:
Table of Contents

Advertisement

CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL

4.8 Enter Site Details

Clicking the Site Config tab displays the Site Config window, which is used to enter the site details
(see FIG.7).
Note: The client and installer details entered in the window are saved in the 'config data file' on the PC
laptop but not saved in the panel's memory.
However, the following lower sections of the window, containing programming data, are saved in
the panel's memory
The Normal String is the text normally shown on the panel's display. This string is limited to 40
characters (including spaces). By default, 'C-TEC CAST XFP Fire Panel' is entered.
The Maintenance String is the text shown on the panel's display when the Maintenance Date
is reached. By default, 'Service Required, Call Engineer' is entered. Typically, set the
maintenance date to 12 months after the commissioning date.
Tick the Send to Panel? box to send these settings when data is saved to the panel.
An Auto Adjust DST (Daylight Saving Time) option is also selectable.
Tick the Send to Panel? box to send the DST setting and the time/date on the PC laptop when
data is saved to the panel.
The default entry codes for Access Level 2 and 3 can be modified. These codes are
automatically sent when data is saved to the panel.
Day and Night times alter the time the panel enters day (building occupied) and night (building
unoccupied) mode. These settings are automatically sent when data is saved to the panel.
Blink Polling LED gives the option to turn the loop devices' polling LED ON/OFF.
Real Time Output of Events option is for future use.
FIG.7 – Site Config Window