CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL
112 devices found
Auto learn complete, Press Accept
Press the Accept  button then press Escape  button x 4 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
AFTER A SUCCESSFUL AUTO ADDRESS YOU WILL HAVE A 'ONE OUT, ALL OUT' FIRE
ALARM SYSTEM.
See Table 1 below for the default device assignment following an auto address.
DEVICE
Loop Smoke/Heat Detectors
Loop Manual Call Points
Loop I/O Unit Inputs
Loop I/O Unit Outputs
Loop Sounders/VADs
Panel Conv. Sounder Circuit 1
Panel Conv. Sounder Circuit 2
Option 2: Select ' Continue from last address? Yes'
Use this option if you do not want to erase the stored loop device data. The panel will start to learn
the loop from the last known address in its memory. Existing data will not be overwritten, e.g. zone
and group allocation, device names, etc., will remain unchanged. The only data that will be
overwritten is device type and whether or not it is fitted.
button to select 'Yes' then press the Accept  button shown below:
Press the scroll
Continue from last address? Yes
The panel will perform an auto address. Wait for the process to complete and a brief summary
window will appear, similar to the one shown below:
112 devices found
Auto learn complete, Press Accept
Press the Accept  button then press Escape  button x 4 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
Page 6 of 16  Commissioning/Programming Quick Start Guide  Approved Document No. DFU5020010 Rev 4
DEFAULT ASSIGNMENT
Zone 1
Zone 1
Zone 1
Set 1
Group 1
Group 1
Group 2
Table 1 : Default Device Assignment
Assignment Terms:
Input devices such as detectors, MCPs and the
input channels of I/O units are programmed to
be members of a Zone.
Output devices such as loop powered sounders
and the panel's conventional sounder circuits
are programmed to be members of a Group.
The output channels of I/O units and panel
relays are programmed to be members of a Set.
Default Cause & Effects (C&E):
Zone 1 triggers Group 1 and Set 1.