Daikin Altherma 3 H MT F Installer's Reference Manual page 145

Hide thumbs Also See for Altherma 3 H MT F:
Table of Contents

Advertisement

EPRA08~12EAV3+W1 + ETVZ12S18+23EA6V+9W
Daikin Altherma 3 H MT F
4P634887-1 – 2021.03
#
Code
[2.6]
[1-06]
[1-07]
[1-08]
[1-09]
Emitter type
Heating up or cooling down the main zone can take longer. This depends on:
The water volume of the system
The heater emitter type of the main zone
The setting Emitter type can compensate for a slow or a quick heating/cooling
system during the heat up/cool down cycle. In room thermostat control, Emitter
type influences the maximum modulation of the desired leaving water
temperature, and the possibility for usage of the automatic cooling/heating
changeover based on the indoor ambient temperature.
It is important to set Emitter type correctly and in accordance with your system
layout. The target delta T for the main zone depends on it.
Description
Set weather-dependent cooling in [2.6] Cooling
WD curve:
T t
[1-08]
[1-09]
[1-06]
[1-07]
T
Target leaving water temperature (main zone)
t
T
Outdoor temperature
a
Set weather-dependent heating in [9.l]
Overview field settings:
[1-06]: Low outdoor ambient temperature.
10°C~25°C
[1-07]: High outdoor ambient temperature.
25°C~43°C
[1-08]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑03]°C~[9‑02]°C
Note: This value should be higher than [1‑09]
as for low outdoor temperatures less cold
water is required.
[1-09]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑03]°C~[9-02]°C
Note: This value should be lower than [1‑08] as
for high outdoor temperatures colder water is
required.
10
Configuration
|
T a
ambient
temperature.
ambient
temperature.
Installer reference guide
145