TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ
Safety Instructions
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
9
www.DeltaPSU.com (July 2019, Rev. 04)
•
ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the device. If mains are not turned OFF,
there is risk of explosion / severe damage.
•
To guarantee sufficient convection cooling, keep a distance of > 40mm
(1.57 inch) above and > 20mm (0.79 inch) below the device as well as a
lateral distance of > 10mm (0.39 inch) to other units. In case the
adjacent device is a heat source, the lateral distance will be > 25mm
(0.98 inch).
•
Note that the enclosure of the device can become very hot depending on
the surrounding air temperature and output load connected to the device.
Risk of burns!
The main power must be turned off before connecting or disconnecting the
•
wires to the terminals!
DO NOT insert any objects into the device.
•
•
Dangerous voltages present for at least 5 minutes after disconnecting all
sources of power.
•
The power supplies unit should be installed in minimum IP54 rated
enclosure.
•
The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is relatively
free of conductive contaminants.