F-Refrigerant Charge and Check - Fin/Tube Coil & RFC
LGH/LCH092H, 102H, 120H, 150S
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system, and add
required nameplate charge.
NOTE - System charging is not recommended below
60_F (15_C). In temperatures below 60_F (15_C), the
charge must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1- Make sure outdoor coil is clean. Attach gauge
manifolds and operate unit at full CFM in cooling mode
with economizer disabled until system stabilizes
(approximately five minutes). Make sure all outdoor air
dampers are closed.
2- Check each system separately with all stages
operating. Compare the normal operating pressures
(see table 18) to the pressures obtained from the
gauges. Check unit components if there are
significant differences.
3- Measure the outdoor ambient temperature and the
suction pressure. Refer to the appropriate circuit
65 F
Suct
(psig)
108
114
Circuit 1
119
125
108
115
Circuit 2
124
131
LGH/LCH150S Normal Operating Pressures - Fin/Tube - RFC
75 F
Disc
Suct
Disc
(psig)
(psig)
(psig)
253
112
295
255
119
296
257
129
303
264
136
308
273
111
314
277
119
318
284
131
327
289
140
334
charging curve to determine a target liquid
temperature.
Note - Pressures are listed for sea level applications.
4- Use the same thermometer to accurately measure the
liquid temperature (in the outdoor section).
D If measured liquid temperature is higher than
the target liquid temperature, add refrigerant to
the system.
D If measured liquid temperature is lower than
the target liquid temperature, recover some
refrigerant from the system.
5- Add or remove charge in increments. Allow the
system to stabilize each time refrigerant is added or
removed.
6- Continue
temperature
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.
7- Example LGH/LCH150 Circuit 1: At 95°F outdoor
ambient and a measured suction pressure of
130psig, the target liquid temperature is 96°F. For a
measured liquid temperature of 106°F, add charge in
increments until measured liquid temperature agrees
with the target liquid temperature.
TABLE 18
Outdoor Coil Entering Air Temperature
85 F
95 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
114
338
117
122
342
125
136
348
141
146
358
155
114
356
117
122
362
125
137
372
141
148
382
155
Page 30
the
process
until
measured
agrees
with
the
105 F
Disc
Suct
Disc
(psig)
(psig)
(psig)
384
119
438
390
127
444
403
145
460
413
161
470
400
119
451
409
128
460
422
145
474
434
160
486
liquid
target
liquid
115 F
Suct
Disc
(psig)
(psig)
122
501
129
501
149
522
167
530
121
508
129
512
147
532
163
541