Basic Procedures
1,2,3...
Data Link Procedure
28
• Connect the communications cables.
2. Set the node address on the front rotary switches.
• 01 to 32
3. Set the baud rate and operating level on the front DIP switch.
• 2 M, 1 M, or 500 Kbps
• Operating level 0 or operating level 1 (C200HX/HG/HE PLCs only)
4. Set the terminating resistance on the sliding switch.
• ON or OFF (Only the end nodes are set to ON.)
5. Connect power to all nodes.
6. Connect the Programming Device to the PLC.
7. Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created
I/O tables have been specified).
8. Register routing tables as required.
CVM1, CV-series, and CS/CJ-series PLCs
1. Perform mounting and wiring.
• Mount to the PLC.
• Connect the communications cables.
2. Set the Unit number on the front rotary switches.
• 00 to 15 (0 to F: CS/CJ-series display is in hexadecimal)
3. Set the node address on the front rotary switches.
• 01 to 32 (01 to 62) (See note a.)
4. Set the baud rate and operating level on the front DIP switch.
• 2 M, 1 M, or 500 Kbps (wired systems only)
5. Set the terminating resistance on the front slide switch.
• ON or OFF (Only the terminal node is set to ON.)
6. Connect power to all nodes.
7. Connect the Programming Device to the PLC.
8. Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created I/
O tables have been specified).
9. Set the Wired Network 62 Node Enable Bit in the DM Parameter Area soft-
ware switches. (See note b.)
• ON (62 nodes max.) or OFF (32 nodes max.)
10. Register routing tables.
Note a) Setting 62 nodes is possible only with the CS1W-CLK21-V1,
CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-CLK23. The Wired
Network 62 Node Enable Bit in the DM Parameter Area software
switches must be set.
b) This setting is valid only with the CS1W-CLK21-V1, CS1W-
CLK23, CS1W-CLK21-V1, and CS1W-CLK23. Reset the power to
the PLC after setting.
Set the data link mode in the data link parameters in the DM area of the star-
tup node to either automatic or manual data link creation using the Program-
ming Device.
Section 1-4