6-6-17 Multiple Forced Status Read - Omron SYSMAC CS1W-RPT01 Operation Manual

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs
Response Block

6-6-17 MULTIPLE FORCED STATUS READ

Command Block
Response Block
23
0A
Command
code
Parameters
23
02
Command
Response
code
code
Note The bits (flags) in the following memory areas can be force-set or force-reset.
Memory area
IR, SR, LR, HR, and AR
areas
Timer/Counter
Reads the forced status of the specified range of words or timers/counters.
23
0A
Command
code
Memory
area code
Response
Beginning
Memory
code
address
area code
Memory area code, Beginning address, Number of units (command,
response): Specify the memory area code, the beginning address in that
area, and the number of words or timers/counters to read. The number of
units can be set from 0001 to 0040 (Hex) (1 to 64 in decimal). The total of 64
continuous bits (for 4 words) for the number of bits or words and the total of 64
units (for 32 words) for the timers/counters can be read at one time.
The actual area, beginning address, and number of units read will be returned
in the response.
Memory Areas
Forced status can be read in the following areas. Refer to 6-6-2 Memory Area
Designations for memory area designations.
Area
IR, SR, LR, HR, and
AR areas
Timer/counter area
Note Forced status is read by words for the IR, SR, LR, HR, or AR area and by bits/
flags for the Timer/Counter area.
Data (response): Forced status is returned beginning from the specified word
or timer/counter. The number of bytes returned will be (the number of units) x
(the number of bytes/unit).
Data
Bit status
Completion Flag status
Beginning
Number of
address
units
Number of
units
Data type
PV of word
Completion Flag status
Section 6-6
Data
Memory area
Number of
code
bytes
80
2
01
1
227