Omron SYSMAC CS1W-RPT01 Operation Manual page 285

Controller link units
Hide thumbs Also See for SYSMAC CS1W-RPT01:
Table of Contents

Advertisement

Data Link I/O Response Time
CS/CJ-series, CVM1, or CV-series PLC Under Synchronous Operation, C200HX/HG/HE
PLC, or CQM1H-series PLC
Maximum Data Link I/O
Response Time
1,2,3...
260
Input
Input ON delay
Program
Communications
cycle time
PLC at node #7
There are three points shown in the diagram above where processing is
delayed, increasing the data link I/O response time.
1. The input arrives in the PLC just after I/O refreshing, causing a delay of up
to one cycle before the input is read into the PLC.
2. Data exchange occurs just after the PLC at node #1 passes the token,
causing a processing delay of up to one communications cycle time until
the next token is received. There is a maximum delay of one communica-
tions cycle after the token is received.
3. At node #7, data from the previous data exchange is still being transferred,
causing a delay of up to one cycle before the input is read into the PLC. (If
the cycle time at node #7 is longer than the communications cycle time, the
processing will be delayed for two cycles.) Also, if the total number of data
link words exceeds the maximum number for a single exchange, the data
exchange will be divided up and there may be a delay of one to two addi-
tional cycles.
The maximum number of words that can be exchanged in a single data ex-
change is approx. 7,800 words for CS/CJ-series PLCs, approx. 3,700
words for CVM1 and CV-series PLCs, approx. 4,000 for C200HX/HG/HE
PLCs, and approx. 1,200 words for CQM1H-series PLCs.
The equation for maximum data link I/O response time is as follows:
Input ON delay
Cycle time of PLC at node #1 × 2
Communications cycle time × 2
PLC cycle time at node #7 × 2 (See note.)
Output ON delay
Total (data link I/O response time)
Note The PLC cycle time when data link words exceed 12,000 using a CS/CJ-
series Controller Link Unit with unit version 1.2 or later is calculated as fol-
lows.
Input device
1 cycle
PLC at node #1
Data link transmission
Program
Output device
Data link I/O response time
1.5 ms
25 ms × 2
22 ms × 2
10 ms × 2 (See note.)
15 ms
130.5 ms
Section 8-3
I/O refresh
Data exchange
1 cycle
Output ON delay
Output