Guidelines When Installing The Drain Piping - Daikin FXDA15A2VEB Installer And User Reference Manual

Vrv system air conditioner
Hide thumbs Also See for FXDA15A2VEB:
Table of Contents

Advertisement

16
|
Unit installation

16.2.3 Guidelines when installing the drain piping

Installer and user reference guide
52
CAUTION
Make sure the installation of the duct does NOT exceed the setting range of the
external static pressure for the unit. Refer to the technical datasheet of your
model for the setting range.
Make sure to install the canvas duct so vibrations are NOT transmitted to the
duct or ceiling. Use a sound-absorbing material (insulation material) for the lining
of the duct and apply vibration insulation rubber to the hanging bolts.
When welding, make sure NOT to spatter onto the drain pan or the air filter.
If the metal duct passes through a metal lath, wire lath or metal plate of the
wooden structure, separate the duct and wall electrically.
Install the outlet grille in a position where the airflow will not come into direct
contact with people.
Do NOT use booster fans in the duct. Use the function to adjust the fan rate
setting automatically (see
The ducting is to be field supplied.
1 Air inlet side. Connect the inlet side flange (field supply) to the indoor unit,
use screws from accessory (table below). Connect the canvas duct to the
inside of the inlet side flange. Connect the duct to the canvas duct.
10~32
16
2 Air outlet side. Connect the canvas duct to the inside of the outlet side flange.
Connect the duct to the canvas duct.
a
d
e
f
a
Screws for duct flanges
For air inlet side: accessory
For air outlet side: on the unit
b
Flange
For air inlet side: field supply
For air outlet side: on the unit
c
Indoor unit
d
Insulation (field supply)
e
Canvas duct (field supply)
f
Aluminium tape (field supply)
3 Wind aluminium tape around the flange and duct connection on both sides.
Make sure there are no air leaks at any other connection.
4 Insulate the duct to prevent condensation from forming. Use glass wool or
polyethylene foam 25 mm thick.
Filter. Be sure to attach an air filter inside the air passage on the intake side. Use
an air filter with dust collecting efficiency ≥50% (gravimetric method). The
included filter is not used when the intake duct is attached.
Make sure condensation water can be evacuated properly. This involves:
General guidelines
Connecting the drain piping to the indoor unit
"20.1 Field
setting" [
Number of screws according to class
40~50
22
b
c
b
f
4
 69]).
63
26
a
e
d
VRV system air conditioner
4P599621-1A – 2020.10
FXDA10~63A2VEB