Specific installer safety instructions

3.1 Instructions for equipment using R32 refrigerant

Installer and user reference guide
14
CAUTION
Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See
technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
Do NOT pierce or burn.
Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation (for example national gas regulation) and
are executed only by authorised persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;
air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10