16
|

Unit installation

16 Unit installation
In this chapter

16.1 Preparing the installation site

16.1.1 Installation site requirements of the indoor unit

Installer and user reference guide
46
16.1
Preparing the installation site ................................................................................................................................................
16.1.1
Installation site requirements of the indoor unit ..................................................................................................
16.2
Mounting the indoor unit.......................................................................................................................................................
16.2.1
Guidelines when installing the indoor unit............................................................................................................
16.2.2
Guidelines when installing the ducting..................................................................................................................
16.2.3
Guidelines when installing the drain piping ..........................................................................................................
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and
siloxane.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
INFORMATION
Also read the general installation site requirements. See the
4
precautions" [
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.
Do NOT install the unit in the following places:
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
 5]" chapter.