To Connect The Electrical Wiring To The Indoor Unit - Daikin FXDA15A2VEB Installer And User Reference Manual

Vrv system air conditioner
Hide thumbs Also See for FXDA15A2VEB:
Table of Contents

Advertisement

18.2 To connect the electrical wiring to the indoor unit

FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
It is important to keep the power supply and the transmission wiring separated
from each other. In order to avoid any electrical interference the distance between
both wirings should ALWAYS be at least 50 mm.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
1 Remove the service cover.
a c
A
Outside the unit
B
Inside the unit
a
Service cover
b
Connection of power supply
c
Wiring diagram
d
Connection of transmission and user interface wiring
e
Sealing material (accessory)
f
Opening for cables
g
Wire
2 User interface cable: Route the cable through the frame, connect the cable to
the terminal block (symbols P1, P2) and fix the cable with a tie wrap.
3 Transmission cable: Route the cable through the frame, connect the cable to
the terminal block (make sure the symbols F1, F2 match with the symbols on
the outdoor unit), and fix the cable with a tie wrap.
4 Power supply cable: Route the cable through the frame and connect the
cable to the terminal block (L, N, earth).
a
Circuit breaker
b
Residual current device
18
d
b
e
g
g
a
b
Electrical installation
|
e
f
A B
Installer and user reference guide
65

Advertisement

Table of Contents
loading

Table of Contents