Daikin FXDA15A2VEB Installer And User Reference Manual page 71

Vrv system air conditioner
Hide thumbs Also See for FXDA15A2VEB:
Table of Contents

Advertisement

(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
: Default
FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10
Setting: Thermostat differential changeover (if remote sensor is used)
If the system contains a remote sensor, set the increase/decrease increments.
If you want to change increments to...
1°C
0.5°C
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating setpoint in
automatic mode (availability depends on the system type). Differential is cooling
setpoint minus heating setpoint.
If you want to set...
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C
Setting: Auto-restart after power failure
Depending on the needs of the user, you may disable/enable the automatic restart
after a power failure.
If you want auto-restart after power failure...
Disabled
Enabled
(1)
Then
M
SW
12 (22)
4
01
02
03
04
05
06
07
08
20
Configuration
|
(1)
Then
M
SW
12 (22)
2
Example
cooling 24°C/heating 24°C
cooling 24°C/heating 23°C
cooling 24°C/heating 22°C
cooling 24°C/heating 21°C
cooling 24°C/heating 20°C
cooling 24°C/heating 19°C
cooling 24°C/heating 18°C
cooling 24°C/heating 17°C
(1)
Then
M
SW
12 (22)
5
Installer and user reference guide
01
02
01
02
71