General guidelines
To connect the drain piping to the indoor unit
FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10
Checking for water leaks
Pipe length. Keep drain piping as short as possible.
Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe of 20 mm nominal diameter and 26 mm outer diameter).
Slope. Make sure the drain piping slopes down (at least 1/100) to prevent air
from being trapped in the piping. Use hanging bars as shown.
a
Hanging bar
O
Allowed
X
Not allowed
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
Rising piping. If necessary to make the slope possible, you can install rising
piping.
-
Drain hose inclination: 0~75 mm to avoid stress on the piping and to avoid air
bubbles.
a
b
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe nominal Ø20 mm and outer Ø26 mm)
d
Hanging bars (field supply)
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with the correct gauge for the operating capacity of the units.
a
T-joint
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
1~1.5 m
a
≤300
1000~1500
a
b
c
d
a
16
Unit installation
|
(mm)
d
(mm)
Installer and user reference guide
53