General guidelines
To connect the drain piping to the indoor unit
FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10
▪
Checking for water leaks
▪
Pipe length. Keep drain piping as short as possible.
▪
Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe of 20 mm nominal diameter and 26 mm outer diameter).
▪
Slope. Make sure the drain piping slopes down (at least 1/100) to prevent air
from being trapped in the piping. Use hanging bars as shown.
a
Hanging bar
O
Allowed
X
Not allowed
▪
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
▪
Rising piping. If necessary to make the slope possible, you can install rising
piping.
-
Drain hose inclination: 0~75 mm to avoid stress on the piping and to avoid air
bubbles.
a
b
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe nominal Ø20 mm and outer Ø26 mm)
d
Hanging bars (field supply)
▪
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with the correct gauge for the operating capacity of the units.
a
T-joint
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
1~1.5 m
a
≤300
1000~1500
a
b
c